One AirThermica. All seasons.
AirThermica fan coil units are developed for integration with heat pumps, boilers, solar thermal and centralized systems, providing energy-efficient indoor comfort throughout the year. Equipped with a brushless motor and 4-speed fan control, they ensure optimized airflow, low energy consumption and precise temperature management.
Fan coil units for heating, cooling and dehumidification.
Available in 3 options: 400 | 600 | 800.
Operating modes: Heating and Cooling.
2-pipe connection
Integrated Wi-Fi control with MyTESY app and Google Home integration.
Group control for simultaneous management of multiple units.
Brushless motor with 4-speed fan control.
Boost mode for faster reaching of the desired temperature.
Anti-frost protection function.
Self-diagnostic system for fault detection.
Slim design with only 123 mm depth.
Stylish modern front grid .
Silent operation and modulated airflow.
Left or right hydraulic connections for flexible installation.
Integrated control panel.
Easy maintenance and change of filters
| TIN Code | 306738 (left) / 306749 (right) |
| Range | 800 |
| Model | FCU 01 WH 800 P2 HMI L/ FCU 01 WH 800 P2 HMI R |
| Total cooling capacity ((W 7/12 °C; A 27 °C) (1) EN 1397:2021) | 3.27 kW |
| Water flow (Cooling performances (W 7/12 °C; A 27 °C) (1) EN 1397:2021) | 568 L/h |
| Pressure drop (Cooling performances (W 7/12 °C; A 27 °C) (1) EN 1397:2021) | 15.4 kPa |
| Maximum power consumption (Cooling performances (W 7/12 °C; A 27 °C) (1) EN 1397:2021) | 26 W |
| Maximum sound power (2) (Cooling performances (W 7/12 °C; A 27 °C) (1) EN 1397:2021) | 60.1 dB(A) |
| Maximum sound pressure (2) (Cooling performances (W 7/12 °C; A 27 °C) (1) EN 1397:2021) | 56.1 dB(A) |
| Heating capacity ((W 45/40 °C; A 20 °C) (3) EN 1397:2021) | 3.47 kW |
| Water flow (Heating performances (W 45/40 °C; A 20 °C) (3) EN 1397:2021) | 598 kW |
| Pressure drop (Heating performances (W 45/40 °C; A 20 °C) (3) EN 1397:2021) | 15.5 kPa |
| Maximum power consumption (Heating performances (W 45/40 °C; A 20 °C) (3) EN 1397:2021) | 26.5 W |
| Maximum sound power (2) (Heating performances (W 45/40 °C; A 20 °C) (3) EN 1397:2021) | 60.1 dB(A) |
| Coil water content | 1.47 L |
| Maximum operating pressure | 8 bar |
| Hydaulic connections | 3/4 |
| Maximum air flow rate | 522 m³/h |
| Average air flow rate | 373 m³/h |
| Minimum air flow rate | 180 m³/h |
| Maximum static pressure available | - Pa |
| Power supply | 230/1/50 (V/ph/Hz) |
| Total width | 1270 mm |
| Total height | 570 mm |
| Total depth | 123 mm |
| Net weight | 23.2 kg |